PROTECTION BOX P100
APPLICATIONS:
Main protection box for buildings, 3x100A
Prepared for 3 NH00 bases with high cut-off power + neutral base and assembly of equipment on a DIN rail.
Interior or exterior integrated assembly.
MATERIALS:
Box and door made of polyester reinforced with grey self-extinguishing fibreglass, RAL 7035.
Black polyurethane sealant.
APPLICABLE STANDARDS:
EN 62208 e EN61439-2
CHARACTERISTICS:
IP45 IK10
Insulation voltage: 600V
Insulation category: Category II
Temperature range -25 to +60°C.
Thermal dissipation capacity: 13W
Prepared to EDP* lock with cylindrical cannon type RONIS.
*EDP - Energias de Portugal
ASSEMBLY INSTRUCTIONS:
For integrated or surface assembly, after the process of construction of the assembly surfaces.
This product was developed for the introduction of up to 3x100A building power supply cables.
Protection and/or cut-off systems may be installed inside.
The maximum weight of equipment in the interior must not exceed 250 kg/m2 and no heavy item may be assembled on the door.
When cables are passed through the inside wall, orifices must be made at the bottom of the box.
Note: Fixations of NH00 bases can be changed on demand.