COLUMN BOX
APPLICATIONS:
Collective building installation.
Interior integrated assembly.
MATERIALS:
Box and door made of polyester reinforced with self-extinguishing fibreglass, RAL 7035.
Black polycarbonate terminal plate.
APPLICABLE STANDARDS:
EN 62208
CHARACTERISTICS:
06CAQ - IP44 IK10
06CAD - IP43 IK08
Nominal voltage: 400V, 50Hz
Transitory overvoltage (Uimp): 4kV
Overvoltage category: CAT III
Insulation voltage: 600V
Nominal current: 100A
Short-circuit current: According to components.
Neutral regime: TT
Diversity factor (RDF): 0.8 for 4 outputs/ 0.9 for 2 outputs
CEM environment: B
Pollution level: 3
Insulation category: Category II
Internal separation method: Method 1
Connection type: FF
Fixed exterior installation at up to 2000 m high.
Temperature range supported by the housing: -25ºC to +60ºC.
Thermal dissipation capacity: 21W
ASSEMBLY INSTRUCTIONS:
For integrated assembly, after the process of construction of the assembly surfaces.
This product was developed for distributing energy along the upstream column in two units per floor.
Fuses or circuit breakers must be used for this purpose.
The maximum weight of the equipment inside the box must not exceed 280 kg/m2.
No heavy items must be placed on the door.
Options: It can be sold already-equipped.