Go to ParentPanels



MOUNTING EXAMPLES

COLUMN PANELS


APPLICABLE STANDARDS:
EN 61439-4
RTIEBT

CHARACTERISTICS:
General cut-off of 4 pole input.
30 mA differential protection.
Emergency trigger-off system with electromechanical interlock with a general cut-off device.
Incorporated grounding measurement base (feed-through).
Space for energy distributor current limiter.
Casing made of polyester reinforced with grey fibreglass, RAL 7035.
Door with a 3-position lock prepared for installing a barrel.
Energy and grounding protection through glands.
Direct wall fixture or mounting accessories (optional).
Nominal voltage: 400V, 50Hz
Transitory overvoltage (Uimp): 6kV
Overvoltage category: CAT IV
Insulation voltage: 600V
Nominal current: 40 or 63A
Short-circuit current: according to mounted components.
Neutral regime: TT
Diversity factor (RDF): 0.7 for 6 to 9 circuits and 0.8 for 4 to 5 circuits.
CEM environment: B
Pollution level: 3
Protection levels: IP44 / IK10
Insulation category: Category II
Internal separation method: Method 1
Connection type: FF
Fixed exterior installation at up to 2000 m high.

Note:
Configurations upon request.